---
title: "CT ratio and burden: picking a CT that reads correctly"
description: "Why lead resistance dominates the burden on a 5 A secondary, what the S in class 0.5S buys you, and how an oversized ratio quietly loses accuracy at part load."
date: "2026-06-03"
author: "Divakar B"
source: "https://energycalchq.com/blog/ct-ratio-and-burden-for-meters"
license: "© 2026 Divakar B. Quote with attribution to https://energycalchq.com/blog/ct-ratio-and-burden-for-meters"
---

A current transformer is chosen on the ratio, and then everything else is left
to whoever is ordering. That is how a submetering system ends up reading 4 %
low, or reading beautifully at full load and hopelessly at night, with nothing
visibly wrong anywhere.

The ratio is the easy part. The burden and the accuracy class are what decide
whether the number the meter reports is true.

## Burden is a budget, and the cable usually spends it

A CT is a current source. It will push its secondary current through whatever
impedance you connect, developing whatever voltage that takes — up to the point
where the core saturates and it simply cannot. **Burden** is the total impedance
in that secondary loop, expressed in VA at rated secondary current.

Three things spend the budget:

1. The meter or instrument.
2. The **resistance of the leads**, there and back.
3. Terminals, links and test blocks.

Worked through for a 200/5 CT feeding an electronic meter 10 m away on 2.5 mm²
copper:

```
Lead loop      = 20 m of 2.5 mm² ≈ 0.148 Ω
Lead burden    = I²R = 5² × 0.148 = 3.70 VA
Electronic meter                  = 0.50 VA
Terminals and test block          = 0.50 VA
                                    ─────────
Total                             = 4.70 VA  → specify 7.5 VA
```

![Burden budget comparison between a 5 A and a 1 A secondary](/blog/ct-burden-budget.svg "The meter is a rounding error. Nearly 80 % of the burden is cable, and it disappears if you change one specification.")

**The meter is almost irrelevant.** Modern electronic meters draw a few tenths
of a VA; the old moving-iron instruments that made 5 VA meters normal are long
gone. What is left is cable, and cable burden goes with the **square** of the
secondary current.

Which is the entire argument for a 1 A secondary. Same cable, same meter, same
distance:

```
Lead burden at 1 A = 1² × 0.148 = 0.15 VA
Total              = 1.15 VA  → a 2.5 VA CT is ample
```

Twenty-five times less. **Use 5 A secondaries where the CT is close to the
meter, and 1 A wherever the run is long.** Above about 15 m, 1 A is usually the
right answer, and above 30 m a 5 A secondary needs an uncomfortably fat cable to
work at all.

## What happens when you get it wrong

**Under-burdened** — a 15 VA CT operating at 2 VA — is harmless. A CT does not
mind an easy life.

**Over-burdened** is the problem. The CT cannot develop the voltage needed to
drive its rated current through the impedance, so the core saturates. Output
falls below what the ratio promises and the meter reads low. Crucially it reads
low **in proportion to current**, so the error grows as load rises — the readings
are worst exactly when the energy matters most, and they look plausible at every
point.

Nothing alarms. Nothing trips. You find out when someone reconciles submeter
totals against the main meter and finds several per cent missing.

## Accuracy class, and what the S means

| Class | Accuracy | Use |
|---|---|---|
| 0.2S | ±0.2 % | Revenue metering, HT connections |
| 0.5S | ±0.5 % | Sub-billing, tenant metering, energy management |
| 1.0 | ±1.0 % | Indication, general monitoring |
| 3.0 | ±3.0 % | Ammeters only |
| 5P10, 10P20 | Protection classes | Relays — **not** for metering |

The **S** matters more than most specifications acknowledge. A plain class 0.5
CT holds its accuracy from 20 % to 120 % of rated current. A class **0.5S** CT
holds it from **1 %** to 120 %.

For energy monitoring that difference is the whole job. A plant that runs at
15 % load overnight is outside a plain 0.5 CT's specified range for a third of
every day, and those hours quietly accumulate error into the daily total. If you
are metering to allocate cost or to find savings, specify 0.5S.

**Protection CTs are a different device.** 5P10 means 5 % accuracy at 10 times
rated current — they are designed to stay linear during a fault, and they are
deliberately inaccurate at normal load. Never use a protection core for metering.
Where a CT has multiple cores, use the metering core for the meter and the
protection core for the relay, and label them, because a CT with its cores
swapped produces both a bad energy reading and unreliable protection.

## Do not oversize the ratio

The commonest field mistake, and it comes from good intentions: someone fits a
1000/5 CT on a circuit that draws 150 A "for future expansion".

That CT now operates at 15 % of rating. On a plain class 0.5 core, 15 % is below
the specified range and the accuracy is undefined. Even a 0.5S core is working
near the bottom of its range, and the secondary current at 0.75 A is small enough
that noise and terminal resistance become significant.

**Choose the ratio so normal load sits between 40 % and 100 % of the primary
rating.** If you are working from a kW figure rather than a measured current,
convert it first with the [three-phase current
calculator](/tools/three-phase-current) — and use the *running* current, not the
connected load, or you will oversize the CT for exactly the reason above. For a
150 A circuit that is a 200/5, not a 1000/5. If the load will
genuinely grow later, change the CT later — a CT is a cheap component, and the
years of wrong readings in between are not.

The related figure is the **instrument security factor (FS or ISF)**, usually
FS5 or FS10. It says the CT saturates at 5 or 10 times rated current, which
protects the connected meter during a fault. That is a *feature* on a metering
CT and a defect on a protection CT — another reason the two are not
interchangeable.

## Wiring a CT without causing damage

**Never open-circuit an energised CT secondary.** With no burden to drive, the
core drives towards saturation and develops a very high voltage across the open
terminals — hundreds or thousands of volts, capable of killing someone and of
destroying the CT's insulation. Before disconnecting a meter on a live circuit,
**short the CT secondary first**, which is what the shorting links on a test
block are for.

Then get the polarity right. P1/P2 on the primary, S1/S2 on the secondary. A
reversed CT shows negative power on that phase, and on a three-phase meter the
total can look almost credible — low by roughly a third rather than obviously
wrong. Check each phase individually against a clamp meter at commissioning, not
just the total.

Earth the secondary at **one point only**, normally S2 at the meter end. Two
earths make a loop and a path for circulating current.

## Types, briefly

| Type | Notes |
|---|---|
| Solid core (ring) | Cheapest and most accurate. Needs the cable disconnected to fit |
| Split core | Clips around a live cable — retrofits, submetering. Slightly less accurate; the mating faces must be clean and fully closed |
| Rogowski coil | Flexible, no saturation, very wide range. Outputs a voltage, needs an integrator, and the meter must accept it |
| Wound primary | Small primary currents, where a bar CT would be inaccurate |

Split-core CTs deserve one warning: a gapped or dirty mating face adds
reluctance and the CT reads low. If a retrofitted split core reads a few per cent
below a clamp meter, open it and clean the faces before doubting anything else.

## A specification that will read correctly

1. Ratio such that normal load is 40–100 % of primary rating.
2. Class 0.5S for anything used to allocate or analyse energy.
3. Burden calculated — meter plus **lead loop** plus terminals — then round up to
   the next standard VA.
4. 1 A secondary if the run exceeds about 15 m.
5. FS5 or FS10 on metering cores.
6. Shorting-type test block at the meter.
7. Polarity verified per phase at commissioning against a clamp meter.

Once the CT is right, the rest of the chain is the meter and the bus — see
[choosing an energy meter for IoT](/blog/choosing-an-energy-meter-for-iot) and
[Modbus RTU on energy meters](/blog/modbus-rtu-energy-meter-setup). A perfectly
polled register is still a wrong number if the CT feeding it was saturating.
