A cable datasheet looks like a table of facts. It is really a table of
*conditional* facts, and the condition is in a footnote at the bottom of the
page in the smallest type on the sheet. Read the table without the footnote and
you will pick cables that are 20 % adrift and never know it.

This is what each column actually means, and the six places a datasheet catches
people out.

## The footnote is the datasheet

Every current rating on a cable datasheet is published against reference
conditions. The Indian convention:

| Condition | Reference |
|---|---|
| Ambient in air | 40 °C |
| Ground temperature | 30 °C |
| Soil thermal resistivity | 1.2 K·m/W |
| Depth of laying | 0.8 m |
| Grouping | One circuit, isolated |
| Conductor temperature | 70 °C PVC, 90 °C XLPE |

Your installation matches none of those. Every departure needs a correction from
the [derating tables](/blog/cable-derating-factors-table), and the corrections
multiply.

The important discipline: **use the same manufacturer's rating table and
derating factors together.** They are derived from the same test arrangement.
Mixing a rating from one datasheet with a factor from another produces a number
that means nothing, even though both inputs were correct.

![Annotated cable datasheet extract with callouts on the rating columns, volt drop, fault rating and reference conditions footnote](/blog/cable-datasheet-annotated.svg "Four columns and one footnote. The footnote controls all four.")

## Two rating columns, and reading the wrong one

Almost every datasheet publishes at least two current ratings for each size: one
for installation in air, one for direct burial in ground. They differ by 5–15 %,
and which is higher depends on the size.

Small cables often do better in ground, because 30 °C soil is cooler than 40 °C
air. Large cables usually do better in air, because soil conducts heat away
slowly and a big cable generates a lot of it.

There is usually a third distinction for single-core cables: **trefoil** (three
cores in a triangle, touching) versus **flat spaced**. The difference is
significant — flat spaced runs cooler and carries more. If the datasheet gives
both, the installation drawing has to say which arrangement is intended, or the
site will do whatever is easiest and the rating you designed to will not apply.

## Resistance is quoted at two temperatures

You will see two resistance figures and they are not interchangeable:

- **DC resistance at 20 °C** — the manufacturing figure. It is what the cable is
  tested against on the drum, and it is the one quoted in the conductor
  standard.
- **AC resistance at operating temperature** — 70 °C or 90 °C, including skin
  effect and proximity effect.

For a 70 mm² copper conductor the operating figure is roughly 25 % higher than
the 20 °C DC value. Using the 20 °C number for a volt drop calculation
understates the drop by about a quarter, which is exactly the sort of error that
passes review because the arithmetic is correct.

**Skin effect** pushes current towards the outside of a conductor at 50 Hz and
matters above about 185 mm². **Proximity effect** does the same when conductors
run close together. Both are already inside the AC resistance figure — do not
add them again.

## Use mV/A/m for volt drop, not ohms per kilometre

The volt drop column is the one to use, and it is not simply resistance
converted. It bundles three things: resistance at operating temperature,
inductive reactance, and the √3 for a three-phase circuit.

Reactance is why the two are not interchangeable. On small cables resistance
dominates and reactance is negligible. Above roughly 95 mm² reactance becomes a
real share of the total, and on 300 mm² and larger it can dominate — which is
why volt drop stops improving much as you go up in size. Doubling the copper
past that point buys very little.

Some datasheets split the column into `mVr` (resistive) and `mVx` (reactive)
components, with `mVz` as the vector sum. Use `mVz` unless you have a specific
reason to work with the components, and note that the tabulated figure assumes
0.8 power factor unless stated otherwise. At a better power factor the real drop
is slightly lower — a conservative error, but worth knowing when a run is
marginal.

Feed the figure straight into the [voltage drop
calculator](/tools/voltage-drop) rather than deriving it from resistance.

## The short-circuit rating is for one second

The fault column — often `kA for 1 s` — is the current the conductor can carry
for one second before its insulation reaches the damage temperature. Faults are
almost never one second long.

Scale it with the square root of time:

```
I(t) = I(1s) / √t
```

A 70 mm² copper cable rated 8.0 kA for 1 s will take 8.0 / √0.2 = 17.9 kA for
0.2 s. This is the same adiabatic relationship that sizes an
[earthing conductor](/tools/earthing-conductor), applied to the phase conductor.

Two cautions. The time is the **total clearing time** of the protective device,
including its opening time, not the setting on a relay dial. And a
current-limiting device that cuts the fault before the first peak lets through
far less energy than the calculation suggests — if you are relying on that, use
the device's published let-through energy rather than this column.

## Decoding the type designation

Indian cable type codes are systematic once you know the letters. Reading left
to right: conductor, insulation, armour, outer sheath.

| Letter | Means |
|---|---|
| A | Aluminium conductor (no A = copper) |
| Y | PVC — as insulation if it appears before the armour, as sheath if after |
| 2X | XLPE insulation |
| W | Round steel **w**ire armour |
| F | **F**lat steel strip armour |

So:

| Code | Reads as |
|---|---|
| YWY | Copper, PVC insulated, round wire armoured, PVC sheathed |
| A2XFY | Aluminium, XLPE insulated, flat strip armoured, PVC sheathed |
| 2XWY | Copper, XLPE insulated, round wire armoured, PVC sheathed |
| AYY | Aluminium, PVC insulated, unarmoured, PVC sheathed |

Armour choice is not cosmetic. Round wire armour has better tensile strength and
suits vertical runs and direct burial where the cable takes pulling load. Flat
strip armour is cheaper and adequate for horizontal runs on tray.

**Never use steel armour on a single-core AC cable.** The alternating field
induces eddy currents in the steel, which heats up and derates the cable badly.
Single-core cables use aluminium wire armour or none at all — and the same
applies to steel gland plates and steel conduit carrying single cores.

## What else to check before you order

- **Voltage grade.** 1.1 kV is standard for LT. Do not accept 650/1100 V marked
  cable for a 1.1 kV specification without checking which figure is the grade.
- **Number of cores.** 3.5-core has a reduced neutral — fine for balanced
  three-phase loads, wrong where the neutral carries harmonic current from
  VFDs or LED drivers. Then you need a full 4-core.
- **Standard.** IS 1554 Part 1 for PVC, IS 7098 Part 1 for XLPE. A datasheet that
  does not cite one is not a datasheet.
- **Tolerance.** Manufacturers vary 5–10 % on the same nominal construction.
  Design to the datasheet of the cable you will actually buy; if the
  procurement team substitutes a brand, the sizing needs rechecking.
- **Drum lengths.** A 500 m run supplied as two 250 m drums needs a joint, and a
  joint is a maintenance liability and an extra impedance in the fault loop.

Work the sizing through with the [cable sizing
calculator](/tools/cable-size) using the figures from the actual datasheet, and
follow the whole sequence in [how to size a cable
correctly](/blog/how-to-size-a-cable-correctly) — the datasheet is the input to
that process, not a substitute for it.