---
title: "The power factor penalty: what it costs, what fixing returns"
description: "Where reactive power comes from, how Indian tariffs charge for it, and a worked payback on a 200 kW plant — where the penalty is the smaller of the two savings."
date: "2026-05-09"
author: "Divakar B"
source: "https://energycalchq.com/blog/power-factor-penalty-what-it-costs"
license: "© 2026 Divakar B. Quote with attribution to https://energycalchq.com/blog/power-factor-penalty-what-it-costs"
---

Power factor is the only line on an industrial electricity bill that you can
change with a single purchase and see the result the following month. It is
also the one most often left alone for years, because the penalty is buried in
the bill and nobody adds it up.

This is where the reactive power comes from, how the tariff charges you for it,
and a worked payback — including the part that is usually larger than the
penalty itself.

## Where reactive power comes from

Any load with a magnetic field has to build that field up and collapse it every
cycle. The energy sloshes back and forth between the supply and the load without
doing any work. That is reactive power, measured in kVAr, and your cables,
transformer and switchgear have to carry it just the same.

The usual sources, worst first:

| Source | Typical power factor |
|---|---|
| Induction motor at 25 % load | 0.4 – 0.5 |
| Induction motor at full load | 0.85 – 0.88 |
| Welding transformer | 0.4 – 0.6 |
| Distribution transformer, unloaded | very poor, but small |
| Fluorescent with magnetic ballast | 0.5 |
| Induction furnace | 0.7 – 0.8 |
| Resistive heating, incandescent | 1.0 |

**The part-load line is the important one.** A motor's nameplate power factor is
its figure at full load. The same motor running at a quarter of its rating can
sit near 0.5. Plants full of oversized motors — and most plants are — have a
poor power factor for that reason alone, and no amount of capacitor switching
addresses the underlying waste.

## How the tariff charges you

Almost every Indian industrial and commercial tariff does two things at once,
and they are frequently confused:

**1. Demand is billed in kVA, not kW.** This is the big one. The demand charge —
a fixed monthly amount per kVA of contract or recorded demand — is levied on
*apparent* power. Poor power factor inflates the kVA for the same useful work,
so you pay more every month without consuming anything extra.

**2. A power factor penalty or incentive on top.** Typically a penalty below
0.90 that grows as the power factor falls, a neutral band, and a rebate above
0.95. Some states also penalise *leading* power factor.

![Power triangle showing 256 kVA at 0.78 falling to 208 kVA at 0.96, beside the tariff bands](/blog/power-factor-triangle-and-bands.svg "The triangle is the physics; the bands are the tariff. Correcting shortens the hypotenuse, and the hypotenuse is what you are billed on.")

The rates, the bands and the formula differ by state and change with every
tariff order. **Read your own DISCOM's schedule** — what follows is the shape,
not the numbers of any particular utility.

## Worked example: a 200 kW plant

A factory drawing 200 kW at a measured power factor of 0.78.

```
Apparent power now   = 200 / 0.78 = 256 kVA
Reactive power now   = 200 × tan(arccos 0.78) = 160 kVAr

Target 0.96:
Apparent power       = 200 / 0.96 = 208 kVA
Reactive power       = 200 × tan(arccos 0.96) = 58 kVAr

Capacitor required   = 160 − 58 = 102 kVAr
```

So a 100 kVAr bank, near enough, and the plant's apparent demand falls by
48 kVA. The [kW, kVA and kVAr converter](/tools/power-conversion) does this
arithmetic for any load and target.

Now put money against it. Take a demand charge of ₹350 per kVA per month —
**check your own tariff, this varies widely** — and ignore the penalty entirely
for a moment:

```
Before:  256 kVA × ₹350 = ₹89,600 per month
After:   208 kVA × ₹350 = ₹72,800 per month
Saving:                   ₹16,800 per month = ₹2.02 lakh a year
```

Add the penalty that stops being levied, and the incentive that starts being
paid, and the annual figure grows further. Against an installed cost of roughly
₹1.5–2.5 lakh for a 100 kVAr automatic panel, the payback is inside a year on
the demand charge alone.

**Notice which saving is bigger.** Most discussion of power factor is about the
penalty. The penalty is real, but the demand charge on 48 kVA of apparent power
you no longer draw is usually the larger number — and it keeps paying every
month whether or not the penalty band ever applied to you.

## The savings nobody puts in the business case

Three more, all real, none of which appear on the bill as a line item:

**Released capacity.** Those 48 kVA are 48 kVA the transformer, the incomer and
the cables no longer carry. On a plant that is close to its transformer rating,
correcting power factor can defer buying a bigger transformer entirely — which
is a capital saving an order of magnitude above the tariff saving. Check what it
does to your loading with the [transformer sizing
calculator](/tools/transformer-sizing).

**Lower losses.** Cable and transformer copper loss goes with the square of
current. Cutting current by 19 % cuts copper loss by about a third, every hour
the plant runs.

**Better voltage at the far end.** Less current means less volt drop, which
means motors at the end of long runs see closer to their rated voltage and run
cooler.

## Where to connect the capacitors

| Method | Corrects losses in | Best for |
|---|---|---|
| At the motor terminals | Everything upstream, including the final cable | Large motors that run continuously |
| At the distribution board | The submain and above | Groups of smaller motors |
| At the main incomer | Only the utility side | Removing the tariff penalty and nothing else |

Correcting at the incomer fixes the bill. Correcting at the load fixes the bill
*and* the internal losses, and lets you use smaller cable on new circuits. Most
plants end up with a mixture: fixed compensation on the large continuous motors,
and a switched bank at the main board for everything else.

Two cautions on motor-terminal capacitors. Never connect a fixed capacitor on
the motor side of a VFD or a soft starter — it will destroy the drive. And size
motor-terminal capacitors below the motor's magnetising current, or the motor
can self-excite when it is switched off while still spinning.

## Do not chase unity

Correcting to 1.0 is a mistake, for three reasons:

- Beyond unity the power factor goes **leading**, and many tariffs penalise that
  exactly as they penalise lagging.
- A fixed bank sized for full load massively overcorrects at night and at
  weekends, when the plant load falls but the capacitors stay connected.
- Leading power factor causes voltage rise at light load and can resonate with
  system inductance.

Target 0.95 to 0.98 and use an [automatic
panel](/blog/apfc-panel-step-sizing) that switches steps in and out as the load
varies. On a plant whose load swings — most plants — a fixed bank is the wrong
answer even when the total kVAr is right.

## Before you buy anything

1. **Get three bills.** Recorded demand in kVA, average power factor, and any
   penalty or incentive line. That is your baseline and your business case.
2. **Log the load for a fortnight.** A fixed bank suits a steady load; a varying
   load needs steps. The load profile decides which.
3. **Check for harmonics first.** If the plant has significant VFD or rectifier
   load, plain capacitors can resonate with the supply and make things
   dramatically worse. That needs detuned reactors, and it is the subject of the
   [APFC panel post](/blog/apfc-panel-step-sizing).
4. **Size against a target, not against unity.** Work the kVAr out with the
   [power conversion calculator](/tools/power-conversion) at a 0.95–0.98 target.
