---
title: "Voltage drop limits: why lighting gets 3 % and power 5 %"
description: "What IS 732 actually permits, where the two limits come from, and why the same cable can pass for a motor and fail for a lighting board on the same site."
date: "2026-01-20"
author: "Divakar B"
source: "https://energycalchq.com/blog/voltage-drop-limits-is-732"
license: "© 2026 Divakar B. Quote with attribution to https://energycalchq.com/blog/voltage-drop-limits-is-732"
---

Two numbers get quoted on every Indian electrical drawing: 3 % for lighting,
5 % for power. They are correct, but they are quoted as though they were
properties of the cable. They are not. They are properties of what sits at the
end of it, and understanding why they differ is what lets you argue for the
right one when a run is marginal.

This is where the voltage drop limits in IS 732 come from, how to apply them
from the origin of the installation rather than from the nearest board, and the
three situations where meeting them still leaves you with a problem.

## What the limits actually say

IS 732 permits a voltage drop, between the origin of the installation and any
point of utilisation, of:

| Circuit type | Limit | On a 415 V system | On a 230 V system |
|---|---|---|---|
| Lighting | 3 % | 12.45 V | 6.9 V |
| All other uses (power) | 5 % | 20.75 V | 11.5 V |

The words that matter are **origin of the installation**. The limit is not 5 %
per cable. It is 5 % in total, from the incomer to the socket, added up across
every cable in the chain: the submain to the distribution board, the final
circuit from the board, and anything between.

This is the single most common misapplication. A submain that drops 3 % and a
final circuit that drops 3 % have both individually "passed", and together they
have failed. On any installation with more than one level of distribution, set a
budget before you start — 2 % for the submain, 3 % for finals is a common split
— and size to the budget rather than to the headline figure.

![Line chart of voltage falling along a 120 metre run, crossing the 3 percent limit at 64 metres and the 5 percent limit at 106 metres](/blog/volt-drop-along-a-run.svg "The same cable carrying the same current. Only the load at the far end decides which dashed line applies.")

## Why lighting gets the tighter limit

Not because lighting is more delicate, but because of what happens either side
of the limit.

**A motor tolerates a sag and then punishes you for it.** Torque falls with the
square of voltage — 10 % low is 19 % less torque — and to deliver the same
mechanical power the motor draws more current, runs hotter and ages faster. But
it keeps working, and nobody standing next to it can see anything wrong. The
5 % limit is set where that penalty is acceptable rather than where the motor
stops.

**Lighting shows you immediately.** Discharge and fluorescent gear becomes
unreliable at the bottom of its voltage range, and low voltage at the end of a
long circuit is visible as a difference in output between one end of a corridor
and the other. Filament and older halogen sources dim visibly at a few per cent.
The tighter limit is a quality-of-installation limit, not a safety one.

Modern LED drivers complicate this. Most are constant-current with a wide input
range — 140–270 V is typical — and genuinely do not care about a 5 % drop. That
is an argument for relaxing the limit on a specific LED installation with the
designer's justification, not for ignoring the standard by default. The 3 %
figure also has to survive the next refit, when someone puts something else on
that circuit.

## Working it out

For a three-phase circuit, using the mV/A/m figure from the cable table:

```
Vd (volts) = mV/A/m × Ib × L / 1000
Vd (%)     = Vd / nominal voltage × 100
```

`L` is the one-way route length, not the loop length — the table figure already
accounts for the return path. Use the actual routed length including drops and
risers, not the straight-line distance on the layout. Cable routes are typically
20–30 % longer than they look on a plan.

Worked through for the run in the chart: 16 mm² copper, 2.45 mV/A/m, carrying
80 A.

```
Per metre:  2.45 × 80 / 1000       = 0.196 V/m
At 64 m:    0.196 × 64  = 12.5 V   = 3.02 %   ← lighting limit reached
At 106 m:   0.196 × 106 = 20.8 V   = 5.00 %   ← power limit reached
At 120 m:   0.196 × 120 = 23.5 V   = 5.67 %   ← fails either way
```

One cable, one current, three different verdicts depending on where you stop and
what you connected. The [voltage drop calculator](/tools/voltage-drop) does this
against both limits at once.

## When volt drop, not current, picks the cable

On short runs the current rating decides the size. Past a certain length volt
drop takes over, and from then on the cable is bigger than it needs to be for
heating reasons alone.

The crossover is closer than people expect. As a rough guide on 415 V:

| Design current | Volt drop starts governing beyond roughly |
|---|---|
| 20 A | 90 m |
| 50 A | 70 m |
| 100 A | 55 m |
| 200 A | 40 m |

Higher current means the crossover comes sooner, because volt drop scales with
current while the tabulated rating does not scale as fast. On long runs feeding
large loads — a pump house at the back of a plot, a tube well, a remote
compressor shed — assume volt drop will govern and size for it first.

The cheapest fix is usually not more copper. It is moving the distribution
board closer to the load and running the length at a higher voltage or a lower
current. A 20 kW load at 100 m needs a lot of cable; the same load fed from a
board 15 m away, with the length taken up by a lightly loaded submain, needs
far less.

## Three cases where 5 % is not enough

**Motor starting.** The limits above are steady-state. During a direct-on-line
start the motor draws six to seven times full load current, and the drop is six
to seven times as large. A run sitting at 4 % running will see 25 % or worse
during a start — enough to drop out contactors on the same board and enough that
the motor may not accelerate at all. For DOL circuits, check the drop at
starting current, not just at running current. The usual working limit is 15 %
transient at the motor terminals.

**Long cable to a VFD.** The drive rides through supply variation, so the input
cable is rarely the problem. The output cable to the motor is, for entirely
different reasons — reflected wave, dv/dt and charging current — and volt drop
limits are not what governs it.

**The utility's share.** Your 5 % starts at your origin. The DISCOM has its own
tolerance upstream, and IS 12360 permits ±6 % at the point of supply. If the
incoming supply is already sitting 5 % low at peak, your compliant 5 % lands the
far end 10 % below nominal. On sites with known weak supply, measure at the
incomer at the worst hour before you design to the full allowance.

## What to check before you sign it off

- Total drop from the **origin**, not per cable.
- **Routed** length, with drops and risers.
- The **design current**, including the 1.25 factor on motor circuits.
- The right limit for what is actually connected — and remember a mixed board
  gets the 3 % figure for its lighting ways.
- Starting conditions on DOL motor circuits.
- Whether volt drop has pushed the size above what the derated current rating
  required, in which case the cable is volt-drop governed and any change to the
  route matters more than a change to the load.

Size the cable end to end with the [cable sizing
calculator](/tools/cable-size), which checks derated current capacity and volt
drop together and tells you which of the two picked the size, or check an
existing run against both limits with the [voltage drop
calculator](/tools/voltage-drop).
