---
title: "kVA to kW Calculator"
description: "Convert kVA to kW using power factor. Why a 100 kVA generator is an 80 kW machine, the 0.8 convention, and a kVA to kW chart for transformers and DG sets."
standard: "P = S × PF"
source: "https://energycalchq.com/tools/kva-to-kw"
---

A 100 kVA generator is not a 100 kW generator. The gap between the two numbers is power factor, and on a DG set it is the difference between what the alternator can carry and what the engine can burn.

## The formula

```
P = S × PF
```

Where `S` is apparent power in kVA, `PF` is power factor, and `P` is real
power in kW.

That is the whole conversion. No voltage, no √3, no phase — those matter for
current, not for this. kVA and kW are both power; power factor is simply what
fraction of the apparent power does work.

## A worked example

A 100 kVA diesel generator supplying a load at 0.8 power factor:

```
P = 100 × 0.8 = 80 kW
```

Which is why the nameplate on that machine reads **100 kVA / 80 kW**. Two
ratings, one set, and they describe two different limits.

## Why a generator has two ratings

A DG set is two machines bolted together, and each has its own ceiling.

The **alternator** is limited by heating in its windings. Heating follows
current, and current follows kVA — the alternator neither knows nor cares what
the power factor is. Its limit is 100 kVA.

The **engine** is limited by the fuel it can burn and the torque it can
produce. That is real work, measured in kW. Its limit is 80 kW.

Connect a load at 0.8 PF and both limits arrive together: 100 kVA of current
in the windings, 80 kW of work at the crankshaft. The set is perfectly
matched, which is exactly why 0.8 is the convention manufacturers rate to.

Now change the load:

| Load PF | kW delivered at 100 kVA | What limits the set |
| --- | --- | --- |
| 1.0 | 100 kW | Engine — it can only make 80 kW |
| 0.9 | 90 kW | Engine still |
| 0.8 | 80 kW | Both, exactly |
| 0.7 | 70 kW | Alternator |
| 0.6 | 60 kW | Alternator, badly |

At **PF 1.0** the alternator would happily carry 100 kVA, but the engine caps
you at 80 kW. You are paying for alternator capacity you cannot use.

At **PF 0.6** the reverse: the engine is loafing at 60 kW while the alternator
sits at its thermal limit. You bought a 100 kVA set and you are getting 60 kW
of useful work out of it.

This is the practical argument for power factor correction on a site running
on generator supply. Improving PF from 0.7 to 0.9 does not make the engine
bigger — but it lets you draw 80 kW instead of 70 kW from the same machine,
because you stop wasting alternator capacity on reactive current.

## kVA to kW chart

| kVA | PF 0.8 | PF 0.85 | PF 0.9 | PF 0.95 | PF 1.0 |
| --- | --- | --- | --- | --- | --- |
| 5 | 4.0 | 4.3 | 4.5 | 4.8 | 5.0 |
| 10 | 8.0 | 8.5 | 9.0 | 9.5 | 10 |
| 15 | 12.0 | 12.8 | 13.5 | 14.3 | 15 |
| 25 | 20.0 | 21.3 | 22.5 | 23.8 | 25 |
| 40 | 32.0 | 34.0 | 36.0 | 38.0 | 40 |
| 50 | 40.0 | 42.5 | 45.0 | 47.5 | 50 |
| 62.5 | 50.0 | 53.1 | 56.3 | 59.4 | 62.5 |
| 82.5 | 66.0 | 70.1 | 74.3 | 78.4 | 82.5 |
| 100 | 80.0 | 85.0 | 90.0 | 95.0 | 100 |
| 125 | 100 | 106 | 113 | 119 | 125 |
| 160 | 128 | 136 | 144 | 152 | 160 |
| 200 | 160 | 170 | 180 | 190 | 200 |
| 250 | 200 | 213 | 225 | 238 | 250 |
| 320 | 256 | 272 | 288 | 304 | 320 |
| 400 | 320 | 340 | 360 | 380 | 400 |
| 500 | 400 | 425 | 450 | 475 | 500 |
| 625 | 500 | 531 | 563 | 594 | 625 |
| 750 | 600 | 638 | 675 | 713 | 750 |
| 1000 | 800 | 850 | 900 | 950 | 1000 |

The odd-looking ratings — 62.5, 82.5, 125, 320 — are not arbitrary. They are
the kVA sizes that give round kW numbers at 0.8 PF: 50 kW, 66 kW, 100 kW,
256 kW. Manufacturers sell engines in kW and alternators in kVA, and the
catalogue reflects both.

## Transformers work the same way, with one difference

A 100 kVA transformer at 0.8 PF also delivers 80 kW. The arithmetic is
identical.

The difference is that a transformer has no engine. There is no second limit —
the transformer will happily deliver 100 kW into a unity power factor load,
because the only constraint is winding heating, and that is set by current
alone. A transformer's kVA rating is its *whole* rating.

So on a transformer, poor power factor does not waste a kW capability you paid
for. It wastes **current capacity**: reactive current occupies the windings
and the cables feeding them, heats everything on the way, and on a
maximum-demand tariff it shows up on the bill. The [kW, kVA and kVAr
converter](/tools/power-conversion) works out the capacitor rating needed.

## What this means when you are sizing

**Sizing a generator for a known kW load.** Work backwards through the [kW to
kVA calculator](/tools/kw-to-kva), then add margin for motor starting — which
usually governs. A 60 kW load at 0.85 PF needs 70.6 kVA on running load, but
if it includes a 22 kW motor started direct-on-line, the set will need to be
considerably larger to hold voltage through the start. The [DG set sizing
calculator](/tools/dg-sizing) handles that properly.

**Reading a UPS nameplate.** Same conversion, different label. A 1000 VA UPS
at 0.6 PF is a 600 W UPS. See [VA to watts](/tools/va-to-watts).

**Checking a supplier's claim.** If a quotation offers "100 kVA = 100 kW",
someone has confused apparent power with real power. The only load where that
is true is a purely resistive one.

## Common mistakes

**Treating kVA and kW as interchangeable.** They are equal only at unity
power factor, which no industrial load has.

**Applying power factor twice.** If a figure is already in kW, it has had the
power factor applied. Multiplying again by 0.8 halves the answer over two
steps.

**Assuming 0.8 because the nameplate says so.** The 0.8 on a generator plate
is the *rating* power factor, not a measurement of your site. Your actual load
might be 0.75 or 0.95, and the set behaves differently in each case.

**Sizing on running kW only.** Starting kVA can be three to five times running
kVA, and it lasts long enough to dip the voltage across the whole site.
