Skip to content
EnergyCalcHQ
Free · IEC 60617 symbols · planning drawing

Free Single Line Diagram Generator

Enter the panel configuration — HT incomer, transformer, LT incomer and outgoing feeders — and the diagram draws itself as you type. Download it as SVG for a drawing set, or PNG for a quotation. Free, with no sign-up and nothing to install: it runs entirely in your browser, and the configuration never leaves it.

Diagram

11 kVIncoming Feeder from SubstationLASurge arresterIsolatorWith earth switchVCB11 kVCT/PTMetering unitMDMMDM meterABT / tariff630 kVADyn11 · ONAN · 11 kV/415 VBuchholz · OTI / WTI · Neutral CTNACB1000 A incomerCTMFMMFMAAVVEFELRR Y BBus earthSPDN linkMCCB100 AkWhkWh meterLighting Distribution PanelMCCB250 AkWhkWh meterVFD 110 kWMCompressor110 kWMCCB160 Astar-delta 55 kWMCooling Tower Pump55 kWMCB63 AUtility & Spare

HT side

Transformer

Full load current 876 A at 415 V.

Fittings

LT side

Metering, protection & indication

Add-ons

Outgoing feeders

4 of 20

Component schedule

ItemDetailQty
Lightning / surge arrester11 kV station class, at incoming termination1
HT isolatorLoad-break isolator with earth switch1
HT breaker — VCB11 kV · Incoming Feeder from Substation1
HT metering unitCT/PT metering cubicle1
MDM / ABT tariff meterUtility tariff metering on CT/PT secondaries1
Distribution transformer630 kVA · Dyn11 · ONAN · 11 kV/415 V · FLC 876 A1
Transformer fittingsBuchholz relay, OTI / WTI, Neutral CT1
LT incomer — ACB1000 A1
Metering CT setClass 0.5 metering core1
Multifunction meter (MFM/MDM)kW, kWh, PF, THD on incomer1
Ammeter & voltmeterWith phase selector switches1
Indication lampsR / Y / B phase indication1
Earth fault relayELR with core-balance CT1
Surge protection deviceType 2 SPD on LT bus1
Neutral link / neutral busBolted link1
MCCB — Lighting Distribution Panel100 A · Sub-distribution panel1
Energy meter — Lighting Distribution PanelkWh meter on outgoing feeder1
MCCB — Compressor250 A · VFD · 110 kW1
Energy meter — CompressorkWh meter on outgoing feeder1
MCCB — Cooling Tower Pump160 A · star-delta · 55 kW1
MCB — Utility & Spare63 A · Direct outgoing1
EarthingTransformer neutral and LT busbar earth1

What this draws

One HT incomer, one transformer, one LT panel, and up to twenty outgoing feeders — the shape of the great majority of industrial and commercial LT installations. Optionally a bus coupler with a second source, a DG set through an interlocked changeover, and an APFC capacitor bank on the bus.

It deliberately stops there. Ring main topologies, multi-transformer stations and auto-routed layouts are a different problem, and a tool that half-does them produces drawings nobody can trust. What is here is the standard arrangement, drawn to the convention an engineer expects to read: source at the top, transformer in the middle, busbar across, feeders hanging beneath it.

Reading the diagram

The symbols follow IEC 60617 closely enough to be read by anyone who works from single line diagrams: two interlinked circles with a delta above a star for a Dyn transformer, a circle with a G for the generator, a box with a diagonal for a breaker, paired loops on the line for instrument transformers, and the three diminishing bars for earth.

The HT breaker is drawn heavier than the LT devices, and feeder devices smaller again, so the voltage level of a symbol is apparent before you read its label. Every symbol carries its rating and type beside it, and feeder names are set at an angle so a long label cannot collide with its neighbour however tight the spacing becomes.

The checks it runs

The warnings under the diagram are advisory and never block the drawing — a single line diagram gets sketched long before the numbers are settled. It flags an LT incomer rated below the transformer's full load current, an incomer more than twice it, a DG set larger than the transformer, and feeder ratings summing to more than 1.5× the transformer.

That last one deserves explaining. Feeder ratings always over-sum, because every feeder is sized for its own peak and they never peak together — that is what diversity is. A total of 1.2× the transformer is ordinary. Past about 1.5× it stops looking like diversity and starts looking like an undersized transformer or a mistyped rating, which is where the warning appears. Use the breaker sizing calculator to check individual ratings against their cables.

What a single line diagram leaves out on purpose

The word single is doing the work. A three-phase feeder is drawn as one line, and the diagram says nothing about which phase a load sits on or how the board is balanced across them. That is deliberate: the SLD exists to show the topology of the distribution — what feeds what, through which device, at which rating — and adding three conductors to every run would bury that under detail nobody reads at this stage.

Several other things are outside its scope by convention. Control wiring, interlocks and trip circuits belong on a schematic, not here. Physical arrangement, panel dimensions and cable routes belong on a general arrangement drawing and a cable schedule. Earthing is usually shown only at the transformer star point and the main earthing terminal, with the protective conductor for each circuit left to the cable schedule.

Knowing that boundary is what makes the drawing useful. An SLD asked to carry construction detail stops being readable as a system overview, which is the one job no other drawing in the set does.

The conventions a reviewer will expect

Symbol shapes vary between standards, and the two you will meet in India are IS 12032, which follows IEC 60617, and the ANSI set that arrives with American equipment documentation. They are not interchangeable, and the most common cause of a drawing being queried is mixing them — an IEC circuit breaker symbol on the incomer and an ANSI one on a feeder in the same diagram.

Beyond symbols, a reviewer is looking for a small number of things to be present. Every device wants a rating and a unique reference. Every cable wants a size, a core count and a length. The transformer wants its rating, both voltages, its vector group and its per cent impedance, because those four values are what anyone checking the fault level will need. Power should flow top to bottom or left to right consistently, and the supply should enter at a single, obvious point.

Where a drawing is going to a utility or an electrical inspector for approval, expect the prospective fault current at the main board to be stated explicitly, along with the breaking capacity of the incoming device. Those two numbers together are what demonstrate the switchgear can clear a fault, and a drawing that omits them is usually returned before anything else on it is read.

Questions people ask

What arrangement will this draw, and what will it not?
One HT incomer, one transformer, one LT panel and up to twenty outgoing feeders — the shape of the great majority of industrial and commercial LT installations — optionally with a bus coupler and second source, a DG set through an interlocked changeover, and an APFC bank on the bus. It stops there deliberately. Ring main topologies, multi-transformer stations and auto-routed layouts are a different problem, and a tool that half-does them produces drawings nobody can trust.
Why does it warn that my feeder ratings add up to more than the transformer?
Because past a point that stops looking like diversity. Feeder ratings always over-sum, since every feeder is sized for its own peak and they never peak together — a total of 1.2 times the transformer is ordinary. The warning appears past about 1.5 times, where the more likely explanations are an undersized transformer or a mistyped rating. All the checks are advisory and none of them block the drawing, because an SLD gets sketched long before the numbers are settled.
Why is a three-phase feeder drawn as one line?
Because the word single is doing the work. The diagram exists to show the topology of the distribution — what feeds what, through which device, at which rating — and adding three conductors to every run would bury that under detail nobody reads at this stage. It follows that the SLD says nothing about which phase a single-phase load sits on or how the board is balanced, and it is not the drawing to check that on.
What belongs on a single line diagram and what belongs elsewhere?
Control wiring, interlocks and trip circuits belong on a schematic. Physical arrangement, panel dimensions and cable routes belong on a general arrangement drawing and a cable schedule. Earthing is usually shown only at the transformer star point and the main earthing terminal, with each circuit's protective conductor left to the schedule. Knowing that boundary is what keeps the drawing useful — an SLD asked to carry construction detail stops being readable as a system overview, which is the one job no other drawing in the set does.
Which symbol set should I use — IEC or ANSI?
Either, consistently. The two you will meet in India are IS 12032, which follows IEC 60617, and the ANSI set that arrives with American equipment documentation. They are not interchangeable, and the commonest cause of a drawing being queried is mixing them — an IEC breaker symbol on the incomer and an ANSI one on a feeder in the same diagram. Beyond symbols, a reviewer wants every device to carry a rating and a unique reference, every cable a size, core count and length, and the transformer its rating, both voltages, its vector group and its per cent impedance, because those four are what anyone checking the fault level needs.

Next steps

This is a simplified representation for planning purposes only. Final SLDs must be verified and stamped by a licensed electrical engineer before use in actual installation or approval submissions.