Skip to content
EnergyCalcHQ
IEC 61869-2 · class 0.5S

CT Ratio & Burden Calculator

The ratio is the easy half. This also budgets the burden — which on a 5 A secondary is mostly cable, not meter — and checks the normal load sits high enough up the CT's range for its accuracy class to mean anything.

Circuit

Secondary

Secondary wiring

CT ratio
200/5A
Normal load sits at 70 % of rating, inside the 40–100 % band where the accuracy class applies.
Specify a CT of at least
5VA
Total burden 4.70 VA, of which the leads are 79 %.
Lead loop resistance0.148Ω
Burden from leads3.70VA
Burden from meter0.50VA
Terminals and links0.50VA
Total burden4.70VA
Secondary current at normal load3.50A
Same job on a 1 A secondary1.15VA

For page numbers, keep Headers and footers ticked under More settings in the print dialog.

Pick the ratio for the load you have

The commonest field mistake comes from good intentions: fitting a 1000/5 CT on a circuit drawing 150 A “for future expansion”. That CT now runs at 15 % of its rating, which for a plain class 0.5 core is below the range its accuracy is specified over. The readings are not slightly worse — they are undefined.

Choose the ratio so normal running current lands between 40 % and 100 % of the primary rating. For a 150 A circuit that is a 200/5, not a 1000/5. A CT is a cheap component; change it when the load actually grows, rather than accepting years of poor readings in between.

Burden is a budget, and cable spends most of it

A CT is a current source. It drives its secondary current through whatever impedance you connect, developing whatever voltage that takes — until the core saturates and it cannot. Burden is that total impedance, expressed in VA at rated secondary current.

Lead loop  = 2 × ρ × L / A          ρ = 0.01851 Ω·mm²/m copper
Lead VA    = I² × R
Total VA   = lead VA + meter VA + terminals

Modern electronic meters draw a few tenths of a VA. The 5 VA instruments that made large CTs normal are long gone. What is left is almost entirely cable — and cable burden goes with the square of the secondary current.

Which is the whole argument for a 1 A secondary. Same cable, same meter, same distance, and the lead burden falls twenty-five fold. Use 5 A where the CT is close to the meter; above about 15 m, 1 A is usually the right answer, and above 30 m a 5 A secondary needs uncomfortably fat cable to work at all.

What over-burdening actually does

Under-burdening is harmless — a 15 VA CT running at 2 VA does not mind. Over-burdening saturates the core, so the CT cannot deliver its rated secondary current and the meter reads low.

The dangerous part is the shape of the error: it grows with current. The readings are worst exactly when the energy matters most, and they look entirely plausible at every point. Nothing alarms, nothing trips, and you find out when somebody reconciles submeter totals against the main meter and finds several per cent missing.

Accuracy class, and the S

ClassAccuracyHolds from
0.2S±0.2 %1 % of rating
0.5S±0.5 %1 % of rating
0.5±0.5 %20 % of rating
1.0±1.0 %20 % of rating
5P10, 10P20Protection classesNot for metering

The S is worth more than most specifications acknowledge. A plain class 0.5 CT holds its accuracy from 20 % of rating; a class 0.5S holds it from 1 %. On a plant that idles overnight, that difference is a third of every day spent outside specification. If the metering allocates cost or hunts for savings, specify 0.5S — and see what it is worth with the metering accuracy calculator.

Protection cores are a different device. 5P10 means 5 % accuracy at ten times rated current: designed to stay linear during a fault and deliberately inaccurate at normal load. Never meter from one.

Wiring, and the one that hurts

Never open-circuit an energised CT secondary. With no burden to drive, the core saturates and develops hundreds or thousands of volts across the open terminals — enough to kill somebody and enough to destroy the CT's insulation. Short the secondary before disconnecting a meter on a live circuit. That is what the shorting links on a test block are for, and it is why a test block is not an optional extra.

  • Polarity. P1/P2 primary, S1/S2 secondary. A reversed CT shows negative power on that phase, and a three-phase total that is low by roughly a third rather than obviously wrong. Check each phase against a clamp meter at commissioning.
  • Earth the secondary at one point only, normally S2 at the meter. Two earths make a loop.
  • Split-core CTs must close fully on clean mating faces. A gapped or dirty joint adds reluctance and the CT reads low — check this before doubting anything else on a retrofit.

A specification that will read correctly

  1. Ratio such that normal load is 40–100 % of primary.
  2. Class 0.5S for anything used to allocate or analyse energy.
  3. Burden calculated — meter plus lead loop plus terminals — then rounded up to the next standard VA.
  4. 1 A secondary if the run exceeds about 15 m.
  5. FS5 or FS10 instrument security factor on metering cores.
  6. Shorting-type test block at the meter.
  7. Polarity verified per phase at commissioning.