Skip to content
EnergyCalcHQ
IEC 60898 · IEC 60947-2 · Ib ≤ In ≤ Iz

MCB & MCCB Sizing Calculator

Rating, trip curve and breaking capacity for a circuit — checked against the cable it protects, and corrected for the temperature inside the panel rather than the temperature the breaker was calibrated at.

Circuit

Start from
Supply

Cable and conditions

MCB rating
63A
Curve C. Ib 53.4 A ≤ In 63 A ≤ Iz 80 A — the cable is protected.
Breaking capacity needed
16kA
Icu at or above the 16.0 kA here. Specify Ics = 100 % of Icu where downtime matters.
Design current Ib53.4A
Ambient factor0.94
Rating needed after ambient56.8A
Actual capacity at this ambient59.2A
Trip curveC
Magnetic pickup630A
I₂ (conventional trip)91.4A

For page numbers, keep Headers and footers ticked under More settings in the print dialog.

A breaker is chosen for the cable, not for the load

This is the idea everything else follows from. The device protects the cable; the load is merely what decides the minimum. The rule that ties them together:

Ib ≤ In ≤ Iz
  • Ib — design current. The breaker must be at least this, or it trips on normal load.
  • In — the device rating.
  • Iz — the cable's current capacity after derating, not the tabulated figure.

Miss the right-hand half and the cable can sit above its rating indefinitely with the breaker perfectly content. A cable protected by a breaker that is too large is not protected at all — and this is the single most common fault in a distribution design, because the left-hand condition alone always looks satisfied.

Note which Iz. Take the tabulated rating, apply the ambient, grouping and installation factors from the cable sizing calculator, and use that. A 70 mm² cable rated 174 A on the table might be 118 A on your tray, and 118 A is the number this rule uses.

The second condition, which only matters for fuses

I₂ ≤ 1.45 × Iz

I₂ is the current that guarantees the device operates within its conventional time — 1.45 × In for MCBs to IEC 60898, 1.30 × In for MCCBs to IEC 60947-2. Because those factors are at or below 1.45, any device satisfying In ≤ Iz satisfies this automatically.

It is worth knowing anyway, because it does not hold for fuses. A gG fuse can have an I₂ of 1.6 × In, so a fuse sized at Iz fails this check and must be taken down a size.

Trip curves

CurveMagnetic tripUse for
B3–5 × InLighting, resistive load, long final circuits
C5–10 × InGeneral mixed load — the default
D10–20 × InMotors, transformers, welding — anything with inrush

The failure people expect is a D curve on a lighting circuit nuisance-tripping. The failure that actually hurts is the opposite: a D-curve device at the end of a long run where the fault current never reaches 10 × In, so the magnetic element never operates and a short circuit is cleared only by the thermal element — seconds later, if at all.

That is why the minimum fault current at the far end of a circuit is worth calculating. It has to exceed the magnetic pickup shown above, with margin.

Breakers derate in a hot panel

A thermal element is a bimetallic strip, and it does not know why it is warm. Manufacturers calibrate at a reference ambient — 30 °C for MCBs, 40 °C for MCCBs — and inside a loaded enclosure the air is well above the room.

Ambient in the panelMCB factorMCCB factor
30 °C1.001.05
40 °C0.941.00
50 °C0.870.90
60 °C0.800.80

A 63 A MCB at 50 °C is a 55 A device. If the load is 58 A it will trip, intermittently, on hot afternoons — and it will test perfectly on the bench every time an electrician takes it out to check.

Motors are the exception

On a motor circuit the overload protection is the starter's relay, not the breaker. The upstream device is doing short-circuit duty only and is deliberately sized above the motor full load current so the starting inrush passes.

The In ≤ Iz limit then applies to the overload relay setting, not to the breaker. Size the whole starter — contactor, relay, breaker and cable — with the motor starter calculator, and prefer an MPCB, which packages an adjustable thermal element with a fixed magnetic element at about 13 × In.

Icu, Ics and Icn

  • Icu — ultimate breaking capacity. The device interrupts this fault once, safely, and may be scrap afterwards.
  • Ics — service breaking capacity. It interrupts and stays fit for service. Quoted as a percentage of Icu.
  • Icn — the rated capacity for MCBs to IEC 60898, typically 6 kA or 10 kA.

Specifying on Icu alone accepts that after a serious fault the device is scrap and possibly no longer protecting anything. On incomers and anywhere downtime is expensive, ask for Ics = 100 % of Icu.

One economy worth knowing: cascading, where an upstream current-limiting device backs up a downstream one so the downstream device can be rated below the prospective fault at its position. It is valid only for combinations the manufacturer has tested and published — you cannot derive it, and you cannot mix brands.