MCB & MCCB Sizing Calculator
Rating, trip curve and breaking capacity for a circuit — checked against the cable it protects, and corrected for the temperature inside the panel rather than the temperature the breaker was calibrated at.
Circuit
Cable and conditions
| Project | Circuit ref | ||
| Prepared by | Date | ||
| Checked by | Date |
MCB & MCCB Sizing Calculator · IEC 60898 · IEC 60947-2 · Ib ≤ In ≤ Iz · EnergyCalcHQ · energycalchq.com
Preliminary calculation. The figures behind it are representative values for the stated conditions, not a substitute for the current edition of the standard or the manufacturer's published data. Verify before issuing for construction. Not a substitute for a qualified engineer or a protection study.
For page numbers, keep Headers and footers ticked under More settings in the print dialog.
A breaker is chosen for the cable, not for the load
This is the idea everything else follows from. The device protects the cable; the load is merely what decides the minimum. The rule that ties them together:
Ib ≤ In ≤ Iz- Ib — design current. The breaker must be at least this, or it trips on normal load.
- In — the device rating.
- Iz — the cable's current capacity after derating, not the tabulated figure.
Miss the right-hand half and the cable can sit above its rating indefinitely with the breaker perfectly content. A cable protected by a breaker that is too large is not protected at all — and this is the single most common fault in a distribution design, because the left-hand condition alone always looks satisfied.
Note which Iz. Take the tabulated rating, apply the ambient, grouping and installation factors from the cable sizing calculator, and use that. A 70 mm² cable rated 174 A on the table might be 118 A on your tray, and 118 A is the number this rule uses.
The second condition, which only matters for fuses
I₂ ≤ 1.45 × IzI₂ is the current that guarantees the device operates within its conventional time — 1.45 × In for MCBs to IEC 60898, 1.30 × In for MCCBs to IEC 60947-2. Because those factors are at or below 1.45, any device satisfying In ≤ Iz satisfies this automatically.
It is worth knowing anyway, because it does not hold for fuses. A gG fuse can have an I₂ of 1.6 × In, so a fuse sized at Iz fails this check and must be taken down a size.
Trip curves
| Curve | Magnetic trip | Use for |
|---|---|---|
| B | 3–5 × In | Lighting, resistive load, long final circuits |
| C | 5–10 × In | General mixed load — the default |
| D | 10–20 × In | Motors, transformers, welding — anything with inrush |
The failure people expect is a D curve on a lighting circuit nuisance-tripping. The failure that actually hurts is the opposite: a D-curve device at the end of a long run where the fault current never reaches 10 × In, so the magnetic element never operates and a short circuit is cleared only by the thermal element — seconds later, if at all.
That is why the minimum fault current at the far end of a circuit is worth calculating. It has to exceed the magnetic pickup shown above, with margin.
Breakers derate in a hot panel
A thermal element is a bimetallic strip, and it does not know why it is warm. Manufacturers calibrate at a reference ambient — 30 °C for MCBs, 40 °C for MCCBs — and inside a loaded enclosure the air is well above the room.
| Ambient in the panel | MCB factor | MCCB factor |
|---|---|---|
| 30 °C | 1.00 | 1.05 |
| 40 °C | 0.94 | 1.00 |
| 50 °C | 0.87 | 0.90 |
| 60 °C | 0.80 | 0.80 |
A 63 A MCB at 50 °C is a 55 A device. If the load is 58 A it will trip, intermittently, on hot afternoons — and it will test perfectly on the bench every time an electrician takes it out to check.
Motors are the exception
On a motor circuit the overload protection is the starter's relay, not the breaker. The upstream device is doing short-circuit duty only and is deliberately sized above the motor full load current so the starting inrush passes.
The In ≤ Iz limit then applies to the overload relay setting, not to the breaker. Size the whole starter — contactor, relay, breaker and cable — with the motor starter calculator, and prefer an MPCB, which packages an adjustable thermal element with a fixed magnetic element at about 13 × In.
Icu, Ics and Icn
- Icu — ultimate breaking capacity. The device interrupts this fault once, safely, and may be scrap afterwards.
- Ics — service breaking capacity. It interrupts and stays fit for service. Quoted as a percentage of Icu.
- Icn — the rated capacity for MCBs to IEC 60898, typically 6 kA or 10 kA.
Specifying on Icu alone accepts that after a serious fault the device is scrap and possibly no longer protecting anything. On incomers and anywhere downtime is expensive, ask for Ics = 100 % of Icu.
One economy worth knowing: cascading, where an upstream current-limiting device backs up a downstream one so the downstream device can be rated below the prospective fault at its position. It is valid only for combinations the manufacturer has tested and published — you cannot derive it, and you cannot mix brands.