Skip to content
EnergyCalcHQ
IS 732 cl. 6.1

Voltage Drop Calculator

Volt drop in volts and percent for a given cable, current and run length — plus the longest run that still passes, and the smallest size that would.

Inputs

Conductor
Voltage drop
1.34%
Within the 5 % limit. Voltage at the load is about 409.4 V.
Drop5.57V
Voltage at load409.4V
Cable mV/A/m0.830
Max run at this size316m
Power lost in cable0.763kW

For page numbers, keep Headers and footers ticked under More settings in the print dialog.

The formula

Vd = (mV/A/m × I × L) / 1000

The mV/A/m figure is published per cable size and already accounts for the √3 in three-phase systems and for the conductor's reactance as well as its resistance. You do not add a √3 on top — a common double-counting error.

The limits

IS 732 permits a total drop of 3 % for lighting and 5 % for other uses, measured from the origin of the installation to the point of use. That budget is for the whole path, not each cable in it. If a submain already uses 2 %, the final circuit has 3 % left of a 5 % allowance.

The lighting limit is tighter because incandescent and some LED drivers visibly dim; motors tolerate a little more but lose torque with the square of voltage.

What excessive volt drop actually causes

  • Motors run hot. Torque falls with the square of voltage. A motor at 90 % voltage produces 81 % torque, so it draws more current to hold the same load, and heats up.
  • Contactors chatter. Coils drop out around 80 % of rated voltage. A long run plus a starting dip can cross that line.
  • Energy is wasted continuously. The drop is resistive loss, paid for every hour the circuit runs.

Fixing a failing run

In rough order of cost-effectiveness:

  1. Move the distribution board closer. Drop is linear in length. Halving the run halves the drop, and it is often cheaper than upsizing a long cable.
  2. Go up a cable size. Straightforward, and the calculator above tells you which size clears the limit.
  3. Run parallel cables. Two cables halve the drop and share the current. Worth it at large sizes where a single cable becomes hard to bend and terminate.
  4. Correct power factor at the load. Less current for the same real power means less drop. Helps the demand charge too.

Starting dip is a separate check

This calculator uses running current. During a direct-on-line start, current is 6–8× and the drop scales with it — a run at 4 % running can dip past 20 % on start. That will not overheat the cable, but it can drop out contactors and dim lighting elsewhere on the board. For a DOL motor on a long run, check the drop at starting current too.

Volt drop adds up along the chain

The limit is not per cable. It is the total from the origin of the installation to the point of use, so a submain that drops 3 % and a final circuit that drops 3 % have each “passed” and together have failed.

On anything with more than one level of distribution, set a budget before you size anything — 2 % for the submain and 3 % for the finals is a common split — and size to the budget rather than to the headline figure.

Where the mV/A/m figure comes from

It is not resistance converted. The tabulated figure already contains three things: conductor resistance at its 70 °C operating temperature, inductive reactance, and the √3 for a three-phase circuit.

Reactance is why you cannot derive it from ohms per kilometre. On small cables it is negligible; above roughly 95 mm² it becomes a real share of the total, and on 300 mm² and larger it dominates — which is why volt drop stops improving much as you keep going up in size. Past that point, more copper buys very little.

When volt drop, not heat, picks the cable

On short runs the current rating decides. Past a crossover length volt drop takes over and the cable is larger than heating alone requires. The crossover arrives sooner than people expect, because drop scales with current while the tabulated rating does not.

Design currentVolt drop governs beyond roughly
20 A90 m
50 A70 m
100 A55 m
200 A40 m

Cheaper fixes than copper

Volt drop is a function of current and length, so both are levers before cross-section is:

  • Move the board. A distribution board nearer the load turns a long heavily-loaded run into a short one plus a lightly-loaded submain.
  • Split the load. Two circuits at half the current each drop half as much over the same distance.
  • Correct the power factor. Less current for the same work is less drop, everywhere upstream of the correction.
  • Check the tap setting. If the whole site sits low, the transformer tap is the fix, not the final circuits.

The budget starts below nominal, not at it

The 3 and 5 per cent limits are measured from the supply terminals, and the supply is not obliged to give you 230 V. Indian distribution standards permit the declared voltage to sit within a band — commonly plus or minus 6 per cent at low voltage — and utilities use it.

So the arithmetic that matters at the far end of the circuit is cumulative. A supply already sitting 6 per cent low, plus a 5 per cent drop through your installation, puts the terminal voltage around 205 V on a 230 V nominal system. Every piece of equipment on that board has to work there, and much of it is specified to tolerate exactly that and no more.

Which is why the volt drop limit is a design budget rather than a performance target — it exists to leave room for a supply that is already at the bottom of its permitted range. Designing to use the full 5 per cent on a rural feeder that habitually runs low is compliant on paper and troublesome in practice, and it is the reason motor contactors drop out on sites where every calculation passed.

Copper is not the same resistance in August

Conductor resistance rises with temperature, and copper changes by roughly 0.4 per cent per degree Celsius. The mV/A/m figures in the tables are quoted at the conductor operating temperature for the relevant insulation — 70 degrees for PVC, 90 degrees for XLPE — not at ambient.

That catches people in both directions. A volt drop measured on a cold circuit first thing in the morning will be lower than the same circuit at full load on a summer afternoon, and the difference between a conductor at 30 degrees and one at 70 is about 16 per cent more resistance. A measurement that passes at commissioning can fail in service without anything having changed.

It also means a lightly loaded cable is being assessed pessimistically. A circuit carrying half its rated current never reaches the tabulated operating temperature, so its actual resistance is lower and the real volt drop is below the calculated figure. Where a design is marginal and the load is genuinely light, correcting the mV/A/m value for the expected conductor temperature is legitimate and is set out in the standards — but it requires knowing the load, and it is not a shortcut to apply to a circuit that might one day run at full rating.

Questions people ask

Do I multiply by root 3 for a three-phase circuit?
No, and doing it is the most common error on this calculation. The published mV/A/m figure for a cable already contains the root 3 for a three-phase circuit, along with the conductor's resistance at its 70 °C operating temperature and its inductive reactance. Adding root 3 on top inflates the answer by 73 per cent and sends you up a size or two for nothing.
Is the limit 3 per cent or 5 per cent, and per cable or in total?
IS 732 permits 3 per cent for lighting and 5 per cent for other uses, and it is the total from the origin of the installation to the point of use — not per cable. A submain that drops 3 per cent and a final circuit that drops 3 per cent have each passed on their own and together have failed. On anything with more than one level of distribution, set a budget first; 2 per cent for the submain and 3 per cent for the finals is a common split.
My run passes at running current. Do I need to check starting as well?
On a DOL motor, yes. This calculator uses running current, and during a direct-on-line start the current is six to eight times that, with the drop scaling right along with it — a run sitting at 4 per cent running can dip past 20 per cent on start. The cable will not overheat in those few seconds, but contactor coils drop out at around 80 per cent of rated voltage, and lighting elsewhere on the board visibly dips.
Why does going up a cable size stop helping on large cables?
Because past a certain size the drop is mostly reactance, and reactance does not fall with more copper. On small cables it is negligible; above roughly 95 mm² it becomes a real share of the mV/A/m figure, and on 300 mm² and larger it dominates. That is the point where parallel cables, a shorter route or power factor correction buy more than another size does.
At what run length does volt drop start deciding the cable size?
Sooner than most people expect, and sooner the higher the current — because drop scales with current while the tabulated rating does not. Roughly: beyond 90 m at 20 A, 70 m at 50 A, 55 m at 100 A and 40 m at 200 A, volt drop governs rather than heating. Below those lengths the current rating picks the size.