Skip to content
EnergyCalcHQ
W = VA × PF

VA to Watts Calculator

You have a VA rating on a nameplate — a UPS, a stabiliser, a small transformer — and you want to know what it will actually run. That answer is in watts, and getting there needs the power factor of the device itself.

Inputs

Real power
860W
Real power0.860kW
Apparent power1.000kVA

For page numbers, keep Headers and footers ticked under More settings in the print dialog.

The formula

W = VA × PF

Where VA is apparent power in volt-amps, PF is power factor, and W is real power in watts.

For the reverse — you know the load and want the rating — use the watts to VA calculator.

A worked example

A 1000 VA UPS with a power factor of 0.6:

W = 1000 × 0.6 = 600 W

So that unit runs 600 W of equipment, not 1000 W. If the nameplate already prints both figures — and it should — use the printed watts and treat this calculation as a check.

What common VA ratings actually deliver

Rating At PF 0.6 At PF 0.7 At PF 0.8 At PF 0.9 At PF 1.0
600 VA 360 W 420 W 480 W 540 W 600 W
800 VA 480 W 560 W 640 W 720 W 800 W
1000 VA 600 W 700 W 800 W 900 W 1000 W
1500 VA 900 W 1050 W 1200 W 1350 W 1500 W
2000 VA 1200 W 1400 W 1600 W 1800 W 2000 W
3000 VA 1800 W 2100 W 2400 W 2700 W 3000 W
5000 VA 3000 W 3500 W 4000 W 4500 W 5000 W
6000 VA 3600 W 4200 W 4800 W 5400 W 6000 W
10 kVA 6000 W 7000 W 8000 W 9000 W 10,000 W

The spread across one row is the whole point. A "1000 VA" unit might run 600 W or 1000 W depending on nothing except its own design, which is why the VA figure alone is not a specification you can buy from.

What that will actually power

Taking a common 1000 VA / 600 W UPS:

Equipment Typical draw Fits in 600 W?
Desktop PC + 24" monitor 200 W Yes, comfortably
Two desktops + monitors 400 W Yes
1U rack server 350 – 500 W One, with little spare
Network switch, 24 port PoE 100 – 400 W Depends entirely on PoE draw
WiFi router + modem 30 W Trivially
NVR + 8 IP cameras 120 W Yes
Laser printer, printing 900 W peak No — never put a laser printer on a UPS
1.5 ton air conditioner 1600 W No
Refrigerator 200 W running, 1200 W starting Marginal — the start is the problem

Two entries there deserve attention. A laser printer draws a large pulse when its fuser heats, and it will overload a UPS sized for the office it sits in — it belongs on a normal socket. A refrigerator or any motor load draws several times its running current at start, so it must be sized on the starting surge, not the running figure.

VA to watts on a stabiliser

Voltage stabilisers are also rated in VA, and the same conversion applies — but with a second consideration.

A 5 kVA stabiliser at 0.8 PF passes 4 kW. However, a stabiliser's rating assumes its input voltage is within its working band. Most units state something like "140 – 280 V input", and their capacity falls as input voltage falls: at 150 V input the transformer is working much harder for the same output, and many units derate substantially. If your supply routinely sags, size on the low-voltage capacity, not the headline figure.

Where the missing power goes

Nothing is lost. The difference between VA and watts is reactive power, measured in VAr:

VAr = √(VA² − W²)

For our 1000 VA unit at 600 W:

VAr = √(1,000,000 − 360,000) = 800 VAr

That 800 VAr is energy moving into the load's magnetic or capacitive fields during part of the cycle and coming back out during the rest. It does no work, but it flows through every conductor and every winding on the way, heating them exactly as much as working current would.

Which is the answer to "why not just rate everything in watts?" — because the conductor, the winding and the switching device do not care whether the current is useful. They only care how much of it there is. That is what VA measures.

Three-phase, briefly

For a three-phase source the conversion is unchanged:

W = VA × PF

Phase only enters when you convert to current. A 10 kVA three-phase supply at 415 V delivers 13.9 A per line; the same 10 kVA single-phase at 230 V delivers 43.5 A. Same apparent power, same watts at a given PF, three times the current. See kVA to amps.

Common mistakes

Assuming VA equals watts. Only true at unity power factor. On a typical UPS you are overstating capacity by 40 %.

Using the load's power factor. For rating a UPS, the UPS's own PF governs. Your load's PF matters for how much current it draws, not for what the UPS can supply.

Sizing on running watts for motor loads. Fridges, pumps and compressors draw a large starting surge. The UPS or stabiliser has to survive that surge, not the running figure.

Reading a peak rating as continuous. Some inverters advertise a surge figure prominently and a continuous one in the small print.

Every conversion on this site runs in your browser — nothing you type is sent anywhere. See all 11 calculators.