Skip to content
EnergyCalcHQ
ISO 8528 · IS 13364

DG Set Sizing Calculator

Size a genset against both things that can decide it — the steady running load and the transient when the largest motor starts — then derate for altitude and ambient, and see what it burns per hour.

Load

Largest motor

Site

DG set required
200.0kVA
Running load governs — needs 192.9 kVA at site conditions. Runs at 80 % load.
Running load126.0kW
Running load157.5kVA
With future margin189.0kVA
Motor starting kVA87.0kVA
Needed for the step load154.8kVA
Altitude derating1.000
Ambient derating0.980
Diesel at this load33.3L/h

For page numbers, keep Headers and footers ticked under More settings in the print dialog.

Two calculations, and you need the larger

Most DG quotations do one sum: add up the load, divide by power factor, add a margin. That covers the set running steadily. It says nothing about the moment a 30 kW motor is switched on, which is when gensets actually misbehave.

Running requirement. Connected load × demand factor, divided by power factor, plus whatever margin you want for future load.

Step-load requirement. Everything already running, plus the starting kVA of the largest motor divided by the transient capability of the alternator. A brushless alternator holds roughly 2.5 times its continuous rating for the second or two a motor takes to run up, with the voltage dip staying inside the 25 % that contactors tolerate. Ask for more than that and the dip drops out every contactor on the board — including the one feeding the motor you were trying to start.

On a plant with one large DOL motor, the second number is usually the larger, and a set chosen on running load alone will fail in service while being entirely correctly sized on paper.

Starting kVA

A motor draws about 6.5 times its full load current on DOL, at a miserable starting power factor. Expressed against the shaft rating, that works out at roughly:

Starting methodkVA per kW of motor
Direct on line8.5
Star–delta2.9
Soft starter3.9
VFD1.5

The commercial consequence is worth spelling out: fitting a soft starter to the largest motor can drop the genset a full frame size or two. The starter is almost always cheaper than the difference — and the smaller set then runs at a healthier load factor for the rest of its life.

Why kVA, not kW

A genset has two ratings and two limits. The engine delivers kW; the alternator is limited by current, so it is rated in kVA at 0.8 power factor. A 100 kVA set gives 80 kW. Run it at 0.7 power factor and the alternator hits its current limit at 70 kW while the engine is still loafing — you paid for engine capacity you cannot use. Correcting power factor on a DG-fed plant frees real capacity.

Note that capacitor banks and gensets need care together: a large fixed bank on a lightly loaded set can drive leading power factor and make the AVR unstable. Switch the bank out when running on DG, or use a controller that does.

Site derating

The engine is an air pump. Thin air means less oxygen, and less oxygen means less power. Standard practice:

  • About 3 % per 300 m of altitude above 1000 m.
  • About 2 % per 5 °C of ambient above 40 °C.

A set installed in Shimla in summer can be 15 % down on its nameplate. The derating applies at the site, so the ordered rating has to be larger than the calculated requirement, not equal to it.

Check the rating definition too. ISO 8528 distinguishes standby (emergency use, no overload capability), prime (unlimited hours with a varying load), and continuous (unlimited hours at constant load). The headline kVA in a quotation is usually the standby figure and the prime rating is around 10 % lower. If the set is your regular supply rather than a backup, size against the prime rating.

Load factor, and why undersizing is not the only sin

An oversized diesel is not harmless. Below about 30 % load a diesel runs cool, fails to burn its fuel completely and wet-stacks: unburnt fuel and carbon build up in the exhaust, the injectors glaze, and maintenance costs climb. Aim for 60–80 % load in normal running.

Fuel consumption is roughly 0.25 litres per kWh at full load, rising towards 0.30 and beyond as the load drops — the figure shown here uses the calculated load point. Over a year of daily running, that gap between a well-loaded set and a lightly loaded one is usually larger than the price difference between the two sets.