Skip to content
EnergyCalcHQ
S = P / PF

kW to kVA Calculator

You know the load in kW. The transformer, the generator and the UPS are all sold in kVA. This is the conversion between what the load does and what the source has to be rated for — and it is where sizing decisions get made.

Inputs

Apparent power
52.33kVA
Apparent power52,326VA
Reactive power26.70kVAr
Phase angle30.7°

For page numbers, keep Headers and footers ticked under More settings in the print dialog.

The formula

S = P / PF

Where P is real power in kW, PF is power factor, and S is apparent power in kVA.

Dividing by a number below 1 always makes the answer bigger. That is the point: the source has to be rated for the current it supplies, and reactive current flows whether or not it does work.

A worked example

A factory with a 45 kW connected load running at 0.86 power factor:

S = 45 / 0.86 = 52.3 kVA

So the supply has to be good for 52.3 kVA, even though only 45 kW does anything useful. The extra 7.3 kVA is the magnetising current the motors need to establish their fields — necessary, but not work.

How much the power factor costs you

Take a fixed 100 kW load and watch what the source has to be rated for:

Load PF kVA required Extra capacity over 100 kW
1.0 100 kVA
0.95 105 kVA 5 %
0.9 111 kVA 11 %
0.85 118 kVA 18 %
0.8 125 kVA 25 %
0.75 133 kVA 33 %
0.7 143 kVA 43 %
0.6 167 kVA 67 %
0.5 200 kVA 100 %

At 0.7 power factor you are buying, installing and paying maximum demand charges on a transformer 43 % larger than the work you are doing requires. At 0.5 you are buying twice the transformer.

This is the entire commercial case for power factor correction. Capacitors are cheap compared with a transformer one frame size larger, a cable one size larger, and a monthly maximum demand charge levied in kVA — which most Indian industrial tariffs are. The kVAr converter sizes the correction; APFC panel step sizing covers building the panel that switches it.

kW to kVA chart

kW PF 0.7 PF 0.8 PF 0.85 PF 0.9 PF 0.95
5 7.1 6.3 5.9 5.6 5.3
10 14.3 12.5 11.8 11.1 10.5
15 21.4 18.8 17.6 16.7 15.8
20 28.6 25.0 23.5 22.2 21.1
30 42.9 37.5 35.3 33.3 31.6
45 64.3 56.3 52.9 50.0 47.4
50 71.4 62.5 58.8 55.6 52.6
75 107 93.8 88.2 83.3 78.9
100 143 125 118 111 105
125 179 156 147 139 132
150 214 188 176 167 158
200 286 250 235 222 211
250 357 313 294 278 263
300 429 375 353 333 316
400 571 500 471 444 421
500 714 625 588 556 526

From kVA to a standard rating

The calculated kVA is a minimum, not a purchase order. Three things happen between the two.

Round up to a standard rating. Transformers come in 25, 63, 100, 160, 250, 315, 400, 500, 630, 1000, 1600 kVA. Our 52.3 kVA lands on a 63 kVA unit.

Add headroom for growth. A transformer sized exactly to today's load has no room for the extension nobody has mentioned yet. 20 % is a common allowance, which would push the same example toward 63 kVA comfortably, or 100 kVA if expansion is genuinely expected.

Apply diversity going the other way. Connected load is not maximum demand — nothing runs everything simultaneously. If your 45 kW is the sum of every nameplate on site, the actual peak is lower, often much lower. See connected load and maximum demand for the factors.

These pull in opposite directions, which is why sizing is judgement rather than arithmetic. The arithmetic just tells you where to start.

Loading a transformer: what to aim for

A transformer is most efficient somewhere near 50 % of its rating, where copper losses (which rise with the square of load) and iron losses (which are constant) balance.

Loading Verdict
Below 30 % Iron losses dominate; you are paying for magnetising an oversized core all day
40 – 70 % The sweet spot — efficient, with room for growth and for motor starts
70 – 85 % Acceptable, running warm, no room for expansion
Above 85 % Winding temperature and life become the concern
Above 100 % Insulation life halves for roughly every 6 – 8 °C over rated temperature rise

So a 52.3 kVA load on a 100 kVA transformer is not oversizing — it is 52 % loading, right in the efficient band.

Sizing a UPS or a generator from kW

UPS. Same conversion, and then a second one. Convert the equipment's watts to VA at the UPS's power factor — which is stated on its nameplate, not on your load's. Then leave headroom: a UPS at 100 % load runs hot, and heat is what kills batteries. See watts to VA.

Generator. Convert to kVA, then check the starting case separately. A DG set that comfortably carries the running kVA can still stall or dip badly when a large motor starts direct-on-line, because starting kVA is three to five times running kVA. The DG set sizing calculator works through both.

Common mistakes

Multiplying instead of dividing. kW to kVA divides by power factor; kVA to kW multiplies. Getting it backwards on a 0.8 PF load gives 64 kVA for a 80 kW load instead of 100 kVA — a 36 % undersize.

Sizing on connected load with no diversity. Adds up to a transformer far larger than the site will ever draw.

Ignoring future load. The cheapest time to install a larger transformer is the first time.

Using the load's power factor for a UPS. The UPS nameplate power factor is the one that governs its own rating.

Every conversion on this site runs in your browser — nothing you type is sent anywhere. See all 11 calculators.